Odor Control and Hydrogen Sulfide Removal with Hydrogen Peroxide
Hydrogen sulfide, H2S, is a common taste and odor compound found in underground potable water sources, characterized by a rotten-egg odor and metallic taste. OxyPure™ successfully oxidizes H2S to remove the taste and odor associated with sulfides. The oxidation reaction can be controlled under alkaline conditions to produce soluble sulfate and a minimal amount of colloidal sulfur. Hence, turbidity is minimized.
H2S + 4 H2O2 → SO4 2- + 4 H2O + 2 H+ (pH > 8) |
Advantages of OxyPure™ Treatment System
- Economical
- Easily administered
- No toxic fumes
- No harmful by-products
| Comparison of OxyPure™ to Other Chemical Removal Systems |
|---|
| | OxyPure™ H2O2 | KMnO4 | Chlorine |
|---|
| Physical Form | Liquid | Solid | Gas |
|---|
| Oxidation Potential | 1.77 V | 1.67 V | 1.36 V |
|---|
| Reaction Time | Minutes | Minutes | Minutes |
|---|
| Product Cost ($/#) | $0.65 * | $1.34 ** | $0.12 ** |
|---|
| Predominant Product | SO4 2- | S, SO4 2- | S, SO4 2- |
|---|
| Decomposition Products | H2O, O2 | MnO2 | Chlorinated Species |
|---|
| Requirement for Removing 1 mg/L H2S: | 4.0 mg/L | 6.2 mg/L | 8.3 mg/L |
|---|
| Dose Rate Cost $/MG | $44.00 | $53.00 | $10.00 |
|---|
* List price for 50% OxyPureTM, bulk tank trucks, as of May 22, 1995
** Chemical Marketing Reporter, May 22, 1995